Technical Resources & Safety Data Sheets
Technical Reference
HVAC Technical Resource Center
Quick-reference safety summaries, pressure-temperature data, cylinder specs, a superheat & subcooling calculator and EPA Section 608 checklists — for every refrigerant HOMETAFY distributes.
- Last updated: August 10, 2026
- 6 refrigerants covered
Safety Data Sheets — Quick Reference
Critical handling, storage and emergency-response information for each refrigerant we distribute. For the full official SDS for a specific lot or cylinder, contact our technical support team.
Pressure-Temperature (PT) Quick Reference
Saturated pressures (psig, sea level) at common coil temperatures. Tap a refrigerant to highlight its column. For R-407C, both dew (vapor) and bubble (liquid) values are shown because of its temperature glide.
| Temp | R-410A | R-134a | R-22 | R-32 | R-404A | R-407Cdew / bubble |
|---|---|---|---|---|---|---|
| 40°F | 119 | 35 | 69 | 121 | 87 | 63 / 80 |
| 60°F | 171 | 57 | 102 | 174 | 126 | 97 / 118 |
| 80°F | 237 | 87 | 144 | 242 | 175 | 141 / 166 |
| 100°F | 319 | 124 | 196 | 326 | 237 | 196 / 226 |
| 120°F | 419 | 171 | 260 | 429 | 312 | 266 / 299 |
Values are approximate industry reference data (psig). Verify against the manufacturer's published PT chart and your system data plate before charging.
Superheat & Subcooling Calculator
Enter your gauge pressure and line temperature. The saturation temperature is interpolated from the PT chart above (valid between 40°F and 120°F saturation).
Superheat
Suction vapor heated above its saturation temperature at evaporator pressure.
- Measure suction-line temperature at the evaporator outlet.
- Convert suction pressure to saturated temperature (PT chart).
- Superheat = suction-line temp − saturated suction temp.
Subcooling
Liquid refrigerant cooled below its saturation temperature at condenser pressure.
- Measure liquid-line temperature at the condenser outlet.
- Convert liquid pressure to saturated temperature (PT chart).
- Subcooling = saturated liquid temp − liquid-line temp.
Cylinder Specifications & Weights
Approximate tare and gross weights. Grey = tare (empty cylinder), green = refrigerant.
EPA Section 608 Compliance Checklist
Tick items off as you go — handy on the job site.
Recovery & Recycling
- Recover refrigerant before opening any part of the system — never vent to atmosphere.
- Use a dedicated, EPA-certified recovery machine and a properly rated recovery tank.
- Never mix different refrigerants in the same recovery tank; cross-contamination ruins reclaim value and can damage equipment.
- Label every recovery tank with refrigerant type, date and technician.
- Send recovered gas to an EPA-certified reclaimer for AHRI-700 re-certification before resale or reuse.
Leak Detection & Repair
- Inspect systems with a charge of 50 lb or more on the schedule required for their appliance type.
- Approved methods: electronic leak detector, soap-bubble solution, ultrasonic detection or pressure-decay testing.
- Check common points: service valves, Schrader cores, flare and brazed fittings, coils and compressor seals.
- Repair leaks within 30 days of detection, or document a retrofit or retirement schedule.
- Re-test the repaired system under pressure before recharging.
Need a reference that's not covered here?
Contact our technical support team for full SDS documents or product-specific data.