HVAC Technical Resource Center

Quick-reference safety summaries, pressure-temperature data, cylinder specs, a superheat & subcooling calculator and EPA Section 608 checklists — for every refrigerant HOMETAFY distributes.

  • Last updated: August 10, 2026
  • 6 refrigerants covered
Section 01

Safety Data Sheets — Quick Reference

Critical handling, storage and emergency-response information for each refrigerant we distribute. For the full official SDS for a specific lot or cylinder, contact our technical support team.

Values are general industry reference data. Always verify against the manufacturer's official SDS and your system's data plate before servicing.
Section 02

Pressure-Temperature (PT) Quick Reference

Saturated pressures (psig, sea level) at common coil temperatures. Tap a refrigerant to highlight its column. For R-407C, both dew (vapor) and bubble (liquid) values are shown because of its temperature glide.

TempR-410AR-134aR-22R-32R-404AR-407Cdew / bubble
40°F11935691218763 / 80
60°F1715710217412697 / 118
80°F23787144242175141 / 166
100°F319124196326237196 / 226
120°F419171260429312266 / 299

Values are approximate industry reference data (psig). Verify against the manufacturer's published PT chart and your system data plate before charging.

Section 03

Superheat & Subcooling Calculator

Enter your gauge pressure and line temperature. The saturation temperature is interpolated from the PT chart above (valid between 40°F and 120°F saturation).

Superheat

Suction vapor heated above its saturation temperature at evaporator pressure.

—Enter values
  1. Measure suction-line temperature at the evaporator outlet.
  2. Convert suction pressure to saturated temperature (PT chart).
  3. Superheat = suction-line temp − saturated suction temp.

Subcooling

Liquid refrigerant cooled below its saturation temperature at condenser pressure.

—Enter values
  1. Measure liquid-line temperature at the condenser outlet.
  2. Convert liquid pressure to saturated temperature (PT chart).
  3. Subcooling = saturated liquid temp − liquid-line temp.
Target ranges vary by equipment — always follow the manufacturer's published charging method. Typical residential split systems run 10–20°F superheat and 8–15°F subcooling. This calculator is a reference aid, not a substitute for the manufacturer's charging chart.
Section 04

Cylinder Specifications & Weights

Approximate tare and gross weights. Grey = tare (empty cylinder), green = refrigerant.

    Tare weights vary by manufacturer and date of manufacture. Always confirm the tare weight stamped on the cylinder before charging.
    Section 05

    EPA Section 608 Compliance Checklist

    Tick items off as you go — handy on the job site.

    0 / 8
    Section 06

    Recovery & Recycling

    • Recover refrigerant before opening any part of the system — never vent to atmosphere.
    • Use a dedicated, EPA-certified recovery machine and a properly rated recovery tank.
    • Never mix different refrigerants in the same recovery tank; cross-contamination ruins reclaim value and can damage equipment.
    • Label every recovery tank with refrigerant type, date and technician.
    • Send recovered gas to an EPA-certified reclaimer for AHRI-700 re-certification before resale or reuse.
    Section 07

    Leak Detection & Repair

    • Inspect systems with a charge of 50 lb or more on the schedule required for their appliance type.
    • Approved methods: electronic leak detector, soap-bubble solution, ultrasonic detection or pressure-decay testing.
    • Check common points: service valves, Schrader cores, flare and brazed fittings, coils and compressor seals.
    • Repair leaks within 30 days of detection, or document a retrofit or retirement schedule.
    • Re-test the repaired system under pressure before recharging.

    Need a reference that's not covered here?

    Contact our technical support team for full SDS documents or product-specific data.